8
|
1
|
Lavatory and vanity sanitized, testing method available and used |
No |
No
|
No |
-Observed sanitizer on 2 of the 3 carts at 50ppm chlorine.
The lavatory, its handles, faucet, and vanity shall be washed using an all purpose cleaner and rinsed daily if the room has been occupied. A sanitizer shall be applied to the lavatory and vanity using a method such as a wipe-on chemically-treated disposable sanitizing towel or equivalent. The sanitizer shall be left to air dry. Sanitizing solutions shall consist of iodophors, quaternary ammonium or other chemicals or methods that are equivalent to the action of 50 parts per million chlorine solution. 15A NCAC 18A .1809 (b). |
|
13
|
1.50
|
Hot and cold running water provided (116-128 F) in guestrooms |
No |
No
|
No |
-Observed the water in 317, 312, 201 at 134F.
Hot water in guest rooms shall be provided at a temperature of no less than 116°F (46.7°C) and no more than 128°F (53.3°C). 15A NCAC 18A .1810 (e). |